Features

The 1.8 million Btu HW 900-2X combines the heating power of the efficient water heater system and two fluid to fluid plate heat exchangers into one ready-to-move trailer package.  The system uses three pumps, one for the water heater’s heating fluid circuit (food grade glycol) and one for each of the two plate heat exchanger output loops.

The water heater is Tri-fuel capable (NG, LP or diesel fuel sources).  Tri-fuel ready units require only a burner change-out to switch from one fuel source to another as all other Tri-fuel plumbing and componentry are permanently in place.  Also, the fuel specific burners have designated storage locations within the HW 900-2X cabinets to ensure convenient hassle-free burner swaps.

As a precautionary measure, an in-line pre-screen acts as a serviceable trap to catch large unforeseen contaminants prior to the plate heat exchangers.  The process water plate exchanger can also be taken apart for removal of scale build-up and cleaning.  Considerable time and effort in the HW 900-2X component layout and trailer access design ensure that general maintenance, burner change-outs and plate heat exchanger services are convenient and practical.

Each plate heat exchanger has a 2 million Btu/h capacity, with a 20% fouling factor to effectively manage the output from the hot water heater.  Therefore, 100% of the heating fluid flow can be directed to one plate heat exchanger.  If your next job requires a different fluid to be heated, the valving can direct the heating fluid to the other plate heat exchanger.  This increases flexibility, reduces cleaning and the risk of contamination.

With two plate heat exchangers, two different fluids can also be heated simultaneously.  Since the two plate heat exchangers are plumbed in parallel, they both will receive heat transfer fluid from the water heater at approx. 180°F.

Specific applications for the HW 900-2X:

  • Acting as a boiler tie-in, heating and circulating a building’s heating fluid for potable hot water and building heat.
  • Heating and circulating potable hot water in a building complex, bypassing the building’s boiler/water heating system.
  • Heating and circulating water for washing facilities at large multiple day events and gatherings.
  • The heating and circulating of water for processing plants, mining and oil field projects.
  • For larger jobs, where one heating unit is not adequate, the HW 900-2X’s plate heat exchanger can be connected in series to boost output.

 

Dimensions:
L 212″ x W 93.5″ x H 114″
Weight 9,000 lbs (estimate)
Burner Two stage

 

 

Fuel Specs:
Diesel
       Input Capacity
• 1,792,000 Btu/h
       Output Capacity
•   1,523,000 Btu/h
    Consumption (max)
• 12.8 US gph

 

Natural gas
  Input Capacity
• 1,690,000 Btu/h
  Output Capacity
• 1,352,000 Btu/h
   Consumption  (max)
• 1,577 cu ft/h

 

Propane
  Input Capacity
• 1,715,000 Btu/h
        Output Capacity
• 1,372,000 Btu/h
      Consumption
(max)
• 18.7 US gph

 

Water heater:
Water jacket/fire tube type
Fluid temperature
Range…………….….130F to 180F

 

 

Controls and monitoring:
Pump and temperature controls, full gauge panel showing circulation fluid temperatures and pressures,
7-light system operation feature for easy troubleshooting

 

Water heater circulation pump:
3 hp, 110 US gpm @ 30 psi
Electrical 230 V, single phase, 60 Hz, 2 x 30 A (L14-30)

 

Internal fluid circulation system:
Basic features
• Atmospherically vented low pressure system with a single supply and return,
adjustable fluid temperature control, auto pressure by- pass for pump protection and variable flow
demands, auto temperature bypass for heat
exchanger protection

 

Plate heat exchangers:
(2) 2million Btu, serviceable,     one for potable and one for process water

 

Plate heat exchanger pumps:
(2) 3 hp, 110 US gpm @ 30 psi

 

Contamination protection:
Pre-screening prior to the plate heat exchangers

 

Quick connect couplers:
2″ Kamlok® couplers

 

Heat transfer fluid (HTF):
Non-toxic propylene glycol/water mixture

 

Loading (standard):
Forklift pockets

 

Loading (optional):
Bolt on lifting frame

 

Certification:
CSA/UL certified

Contact Us